The NCEES specification lists four sub-areas:
Wet pipe, dry pipe, preaction, deluge, water mist, standpipes and water spray — and when each is appropriate.
Water supply, design density and design area, pressure requirements, occupancy hazard classification and hose stream demand.
Sprinklers (K-factor, orientation, response), fire pumps, water storage and valves.
Hydraulic calculations, equipment sizing, and hanger/support requirements.
A sprinkler’s flow follows Q = K√P, where K is the orifice coefficient and P is the pressure at the sprinkler. Using the density/area method, a light-hazard occupancy might require a design density of 0.10 gpm/ft² over the hydraulically most-remote 1,500 ft² design area — so the base demand is 0.10 × 1,500 = 150 gpm before hose stream and friction losses are added.
The textbook covers occupancy classification, the density/area curves, remote-area selection and a full hydraulic walk-through — the skills behind the most heavily weighted questions on the exam.
This is only a preview. The full explanation, diagrams, worked examples and practice problems are in the Fire Protection PE Textbook.